DIY power station

Semi-DIY Power Station for Home Blackout Backup

Version 13. A complete build guide: decisions, calculations, parts, wiring, settings, testing, housing and safe use. What changed in each version is listed in section 24.

Interactive 3D wiring model (12 / 24 / 48 V, 1 to 3 batteries of 50–400 Ah, inverter 1000–5000 W, single box or modular stack, inverter on the floor or wall-mounted with automatic choice of the smallest box, internal or external charger, solar and 12 V/USB on or off, runtime slider, prices and a prebuilt comparison): open the 3D model

Safety: sizing rules, fuses, cables, battery handling, 230 V safety, fire and emergency procedures are in the separate safety guide. Read it before buying parts.

Prices are approximate German/EU street prices as of autumn 2026 and change often. Check current prices before buying. Where a component manual differs from this guide, follow the manual. I'm not an electrician. Anything connected to your house wiring must be done by a licensed electrician (Elektrofachkraft).


Contents

  1. Recommended setup at a glance
  2. 12 V or 24 V
  3. How the AC side works: switchover options
  4. Calculate your blackout loads
  5. Size every component
  6. Bill of materials
  7. Tools and consumables
  8. Battery bank: one battery or several
  9. Wiring diagram
  10. Cable and fuse table
  11. Housing: enclosure, layout and mounting
  12. Build steps
  13. Settings for every device
  14. Commissioning and testing
  15. Using it in a blackout
  16. Earthing, RCDs and gas boilers
  17. Fire safety
  18. Legal and insurance notes for Germany
  19. Maintenance and storage
  20. Common mistakes
  21. Troubleshooting
  22. Alternatives and upgrade paths
  23. Checklists and quick reference card
  24. Revision notes

Item Recommendation
System voltage 24 V
Battery 25.6 V 100 Ah LiFePO4 with built-in BMS (2.56 kWh). Also possible: 50, 200 or 300 Ah per battery (section 5.0). Up to 3 identical batteries in parallel, inside the same box
Charging Internal AC charger, or an external charger plugged into a fused Anderson SB50 charge input (section 3.1). One external charger can serve every battery and module of the same voltage
AC side Option A: Victron MultiPlus inverter/charger with automatic switchover (recommended for blackout backup). Option B: separate pure sine inverter + AC charger (cheaper, manual or always-on)
Inverter size For one 24 V 100 Ah battery: 1500 W (69 A, 100 A battery fuse, 25 mm² main cables; see safety guide section 4). Range: 1000–3000 W (24 V) or 1000–2000 W (12 V). 1000–1500 W is plenty for fridge, freezer, router, lights and boiler, with lower idle draw. Main fuse and cable follow the inverter size (section 5.3)
Solar (optional) MPPT 100/20, up to about 500 W of panels
12 V outputs (optional) DC-DC 24 → 12 V 20 A, fuse block, USB-C PD 100 W, 12 V socket
Protection Battery fuse directly on every battery + terminal, battery switch through the side wall (operable from outside), inline fuse on every branch
Layout Volume-optimised: the 3D model tries floor and wall mounting for the inverter, lengthwise and sideways batteries and several column arrangements, and keeps the smallest inside volume. Box about 57 × 64 × 32 cm with one 100 Ah battery and all options (inverter wall-mounted)
Ventilation Intake grille low next to the inverter, thermostat exhaust fan high on the opposite side wall
Housing One box (1 battery) or a modular stack: battery modules + electronics module on a rolling base (section 11.6). Box building instructions in section 11.5
When to choose 48 V instead More than about 5 kWh or more than 3 kW, or a future whole-house battery (section 2)
Runtime About 18 h per battery at a 100 W average load
Budget About €1,420–2,700 for option B with one 100 Ah battery and all options including two solar panels, €1,080–1,960 without solar and 12 V/USB. Each extra 100 Ah battery adds about €590–870. Option A adds about €400–700

2. 12 V or 24 V

Why voltage matters

Power = voltage × current. At 12 V every watt needs twice the current of 24 V. Current decides cable size, fuse size, heat and losses. Cable losses scale with current squared, so 24 V has about a quarter of the cable losses of 12 V at the same power.

Comparison

12 V 24 V 48 V
Battery for 2.56 kWh 12.8 V 200 Ah 25.6 V 100 Ah 51.2 V 50 Ah
Battery for 5.12 kWh 12.8 V 400 Ah 25.6 V 200 Ah 51.2 V 100 Ah (rack style)
Current at 2000 W ~185 A ~93 A ~46 A
Main cable and fuse at 2000 W 95 mm², 250 A 35 mm², 125 A 16 mm², 60 A
Current at 5000 W not practical not practical (~230 A) ~116 A (50 mm², 150 A)
Sensible max inverter ~1500–2000 W ~3000 W 5000 W and more
Battery fuse type Class T or MRBF Class T (MRBF only if rated) Class T only
12 V devices Run directly DC-DC converter (€30–60) Isolated DC-DC converter (€40–80)
Battery style Box Box Mostly server-rack modules (44 cm wide)
Parts selection and price Largest, cheapest Very good Good for inverters/chargers; fewer small 12 V-style parts
Best for Vans, camping, mostly 12 V loads Home backup, 230 V loads, 1.2–3 kW More than 5 kWh or 3 kW, future home battery

At 48 V the maximum charge voltage is 58.4 V, still below the 60 V DC limit for extra-low voltage. It's safe to touch, but arcs are stronger: use DC-rated parts for at least 60 V (switch, fuses, breakers).

Decision rule

flowchart TD
  A{Is your main output 230 V AC?} -->|No, mostly 12 V devices under 1 kW| V12[12 V]
  A -->|Yes| B{More than about 5 kWh or 3 kW, or a future home battery?}
  B -->|No| V24[24 V: recommended for blackout backup]
  B -->|Yes| V48[48 V]

Don't start at 12 V planning to "upgrade later" by putting batteries in series. You'd have to replace the inverter, charger, MPPT and DC-DC converter.


3. How the AC side works: switchover options

The question is what happens to your fridge and router in the moment the grid fails.

Option B1: separate inverter and charger, manual

flowchart LR
  W1[Wall socket] --> C[Charger] --> B[Battery] --> I[Inverter] --> O[Box outlet]
  W2[Wall socket] --> F[Fridge, normally]
  O -. replug by hand during an outage .-> F

The charger and inverter are two independent devices with no connection between their AC sides. Normally the fridge is plugged into the wall. When the grid fails, the fridge stops, and someone has to unplug it from the wall and plug it into the box. At night or while you're away, it stays off.

Option B2: separate inverter and charger, always-on

flowchart LR
  W[Wall socket] --> C[Charger] --> B[Battery] --> I[Inverter] --> D[Fridge and router, permanently]

Your devices are permanently plugged into the inverter, and the charger keeps the battery full. When the grid fails, the charger simply stops and the battery takes over. No switchover, no interruption.

Pros Cons
Cheapest way to get zero interruption Conversion losses and idle draw 24/7: about 0.4–0.6 kWh/day for a 100 W load, about €50–70/year at €0.35/kWh
Very simple Charger must be larger than the load (15 A × 28 V ≈ 420 W, fine for fridge and router)
Inverter runs constantly, so fan noise and wear

Option B3: separate inverter + automatic transfer switch (ATS)

flowchart LR
  W[Wall socket] --> ATS{Automatic transfer switch}
  I[Inverter, always on] --> ATS
  ATS --> D[Fridge and router]

The ATS (€30–100) feeds your devices from the grid and switches to the inverter when the grid fails. Switching takes about 10–50 ms, usually fine for fridges, sometimes too slow for PCs. A plug-in ATS is fine. A hard-wired one is a job for an electrician. The inverter's idle draw still runs 24/7.

Option A: inverter/charger with automatic switchover (e.g. Victron MultiPlus)

flowchart LR
  W[Wall socket] --> AIN[AC in]
  subgraph MP[MultiPlus inverter/charger]
    AIN --> R{Transfer relay}
    AIN --> CH[Charger]
    INV[Inverter] --> R
  end
  CH --> B[Battery]
  B --> INV
  R --> AOUT[AC out] --> D[Fridge, router, lights]

One device with an AC input (plugged into the wall) and an AC output (your devices):

  1. Grid on: an internal relay connects input to output. Devices run on the grid, the battery is charged, and the inverter is idle.
  2. Grid fails: the unit detects it within milliseconds, opens the relay (which also isolates you from the grid, so nothing feeds back) and starts the inverter. The gap is about 20 ms, too short for a fridge, router or most PCs to notice.
  3. Grid returns: the inverter synchronizes to the grid's phase, closes the relay and hands over without a gap.
  4. PowerAssist: if your load exceeds the set wall-input limit, the battery adds power.

Which to choose

flowchart TD
  Q1{Must the fridge keep running with nobody at home?} -->|No| B1[B1: manual replug]
  Q1 -->|Yes| Q2{Budget for 400 to 700 euro more?}
  Q2 -->|Yes| A[A: MultiPlus with automatic switchover]
  Q2 -->|No| Q3{Accept about 50 to 70 euro per year running cost?}
  Q3 -->|Yes| B2[B2: always-on inverter]
  Q3 -->|No| B3[B3: inverter plus automatic transfer switch]
Option Interruption Extra running cost Extra purchase cost Recommended when
B1 manual Until you replug None None Budget build, someone usually home
B2 always-on None ~€50–70/year None Cheapest zero-interruption option
B3 ATS 10–50 ms ~€30–50/year (idle) €30–100 You already own a separate inverter
A MultiPlus ~20 ms Lowest (inverter idle only during outage) €400–700 more Best for blackout backup

3.1 Charger inside the box or external

The charger doesn't have to live in the box. Instead, fit a DC charge input: an Anderson SB50 panel socket wired through a fuse to the busbars. Any LiFePO4 charger with a matching SB50 plug then charges the whole bank from outside.

flowchart LR
  EC[External LiFePO4 charger] -->|SB50 plug, blue| IN[Charge input socket]
  IN -->|+ through fuse| PB[+ busbar]
  IN -->|−| NB[− busbar, load side of the shunt]
Internal charger External charger + SB50 charge input
Box size and heat Charger column inside Charger column gone (MPPT alone if solar), less heat
Several batteries, modules or boxes One charger per box One charger for all of the same voltage
Upgrading Open the box Swap the charger any time
Blackout readiness Leave the 230 V cable plugged in Leave the external charger plugged in, same effect
Extra parts Fused IEC inlet (€8–15) SB50 socket, fuse and plug (€15–25)

Rules:


4. Calculate your blackout loads

Use the slider in the 3D model to try different average loads quickly. For a real plan, measure.

4.1 Measure, don't guess

Buy a plug-in energy meter (about €15) and measure each device for 24 hours. Fridges and freezers cycle, so a 24-hour reading is far more accurate than the label.

4.2 Load worksheet

Device Running W Start/surge W Hours/day Wh/day (example) Your value
Fridge (modern) 60–100 400–600 cycles 400–700
Freezer 60–100 400–600 cycles 400–700
Router + fibre/DSL modem 10–20 — 24 290
LED lights (4 × 8 W) 32 — 6 190
Phones and laptop (USB-C from the box needs no inverter) 20–65 — 3 150
TV 60–100 — 3 240
Gas boiler controls + circulation pump 60–120 200–300 ~12 (duty) 700–1,000
Inverter idle draw (only while the inverter runs) 10–15 — 24 240–360
Total

Not practical for this system: electric heating, heat pumps, electric water heaters, ovens, induction hobs, washing machines (heating phase).

4.3 Formulas

Usable energy (Wh) = Battery Wh × DoD × Inverter efficiency
                   = 2560 × 0.90 × 0.90 ≈ 2,070 Wh per battery

Runtime (h)        = Usable energy / (Average load W + Inverter idle W)

Batteries needed   = (Daily Wh incl. idle × days of autonomy) / 2,070   → round up

Corrections for real life:

4.4 Worked examples

Scenario Average load 1 battery 2 batteries 3 batteries
Fridge, router, lights 100 W + 12 W idle 18 h 37 h 55 h
Plus freezer 150 W + 12 W 12.8 h 25.6 h 38 h
Plus gas boiler controls/pump 220 W + 12 W 8.9 h 17.9 h 26.8 h

Example: fridge + freezer + router + lights + boiler ≈ 2.6 kWh per day including idle. For 2 days: 2 × 2.6 / 2.07 = 2.5, so 3 batteries, or 2 batteries plus solar.

Stretch tip: a full freezer stays frozen for about 24–48 hours without power. Running it in blocks (2 h on, 4 h off) saves about two thirds of its energy.

4.5 Inverter sizing check

Continuous rating ≥ devices running at the same time × 1.25
Surge rating      ≥ largest start-up surge + everything else running

Example: fridge (100 W, 600 W surge) + freezer (100 W) + boiler (120 W) + lights and router (60 W) = 380 W continuous, 880 W surge. A 1200 W inverter already covers this. Choose 2000 W only if you also want a kettle, microwave or power tools.


5. Size every component

24 V values first, 12 V values in brackets.

5.0 Battery capacity options

Typical LiTime-class LiFePO4 batteries with built-in BMS. Sizes and prices are approximate; check the datasheet of the battery you buy.

System Capacity Energy Size (L × W × H) Weight BMS Inverter it can supply alone Price each
24 V 50 Ah 1.28 kWh 33 × 17 × 22 cm 12 kg 50 A about 1000 W €280–360
24 V 100 Ah 2.56 kWh 53 × 21 × 22 cm 21 kg 100 A about 2000 W €450–600
24 V 200 Ah 5.12 kWh 52 × 27 × 22 cm 38 kg 200 A 3000 W €850–1,100
24 V 300 Ah 7.68 kWh 52 × 27 × 33 cm 57 kg 200 A 3000 W €1,300–1,700
12 V 100 Ah 1.28 kWh 33 × 17 × 22 cm 11 kg 100 A about 1000 W €200–280
12 V 200 Ah 2.56 kWh 52 × 24 × 22 cm 22 kg 200 A 2000 W €400–550
12 V 300 Ah 3.84 kWh 52 × 27 × 22 cm 30 kg 200 A 2000 W €600–780
12 V 400 Ah 5.12 kWh 52 × 27 × 24 cm 40 kg 250 A 2000 W €800–1,050
48 V 50 Ah 2.56 kWh 44 × 30 × 14 cm 24 kg 50 A about 2000 W €550–750
48 V 100 Ah 5.12 kWh 44 × 44 × 14 cm (3U rack) 45 kg 100 A about 4000 W €850–1,200
48 V 200 Ah 10.24 kWh 52 × 44 × 26 cm 85 kg 200 A 5000 W €1,700–2,300

Notes:

5.1 DC current

I_DC = P_AC / (V_min × η)
24 V: 2000 W / (24 V × 0.9) = 93 A
12 V: 1500 W / (12 V × 0.9) = 139 A

Use minimum battery voltage (24.0 V / 12.0 V), because current is highest when the battery is nearly empty.

5.2 BMS check

BMS continuous rating (all batteries together) ≥ I_DC × 1.1
24 V, 1 battery: 100 A ≥ 102 A → borderline at a full 2000 W, fine for typical loads
24 V, 2 batteries: 200 A ≥ 102 A → comfortable
12 V, 1 battery: 200 A ≥ 153 A → OK

See the table in section 5.3 for other inverter sizes.

5.3 Battery fuses and breaking capacity

Fuse ≥ I_DC × 1.25  (next standard size: 60, 80, 100, 125, 150, 175, 200, 250, 300 A)
Cable: smallest cross-section whose derated ampacity is ≥ the fuse rating

Main fuse and cable by inverter size (used in the 3D model):

System Inverter Full-load current Battery fuse (each battery) Main cable Inverter price
24 V 1000 W 46 A 60 A 16 mm² €120–250
24 V 1500 W 69 A 100 A 25 mm² €150–300
24 V 2000 W 93 A 125 A 35 mm² €200–350
24 V 3000 W 139 A 175 A 50 mm² €350–650
12 V 1000 W 93 A 125 A 35 mm² €120–250
12 V 1500 W 139 A 175 A 50 mm² €150–300
12 V 2000 W 185 A 250 A 95 mm² €200–350
48 V 1500 W 35 A 60 A 16 mm² €150–300
48 V 2000 W 46 A 60 A 16 mm² €200–350
48 V 3000 W 69 A 100 A 25 mm² €350–650
48 V 5000 W 116 A 150 A 50 mm² €600–1,100

The main cable includes battery → fuse → switch → busbars → inverter, and every battery-to-collector cable. Check that the batteries' combined BMS current is above the full-load current (section 5.0); if not, the BMS switches off before the inverter reaches full power.

A LiFePO4 battery can deliver several thousand amps into a short, so the battery fuse must be able to break that current:

Fuse type Typical breaking capacity Use as battery fuse?
Class T 20 kA or more at up to 125–160 V DC Yes, the safe choice
MRBF (terminal fuse) About 10 kA at 14 V, lower at higher voltages 12 V: yes. 24 V: only if the datasheet rating at your voltage is enough
ANL / MIDI / MEGA Much lower No, only for branch circuits

With several batteries, every battery gets its own fuse at its + terminal (see section 8).

5.4 Cable cross-section and voltage drop

ΔV = (2 × L × I × ρ) / A
ρ (copper) = 0.0175 Ω·mm²/m, L = one-way length (m), A = cross-section (mm²)

24 V, 35 mm², 1 m, 95 A:  ΔV = 0.095 V (0.4%)
12 V, 70 mm², 1 m, 140 A: ΔV = 0.070 V (0.6%)

Targets: under 1–2% for main and inverter cables, under 3% for branches.

Approximate ampacity, fine-stranded copper, single core, free air at 30 °C. Inside a closed box, derate by about 20%.

Cross-section Approx. ampacity Used for
0.75 mm² 10 A Voltmeter
2.5 mm² 25 A 12 V outputs
4 mm² 35 A Charger (24 V), DC-DC, PV
6 mm² 45 A MPPT (24 V), charger (12 V), 12 V fuse block feed
10 mm² 65 A MPPT (12 V)
16 mm² 100 A MultiPlus 24/1600 DC (check manual)
35 mm² 170–200 A Main cables (24 V)
70 mm² 280–300 A Main cables (12 V)

Use fine-stranded, flexible cable (welding cable, H07RN-F or H07V-K), ideally tinned copper.

5.5 AC charger

Charge time (h) ≈ (Ah × number of batteries) / charger A × 1.05
24 V: 100 Ah / 15 A ≈ 7 h per battery
12 V: 200 Ah / 20 A ≈ 10 h per battery

LiFePO4 usually accepts up to 0.5C (50 A for a 24 V 100 Ah battery). With 2–3 batteries, a 25–30 A charger or a MultiPlus (35–70 A) makes recharging between outages much faster. Check that the total charge current stays within the BMS charge limit of all batteries together.

5.6 Solar MPPT (optional)

MPPT output current = PV watts / charging voltage
24 V: 500 W / 27 V ≈ 18.5 A → 100/20
12 V: 400 W / 13.5 V ≈ 30 A → 100/30

Cold check: Voc_string × 1.15 < MPPT max PV voltage (100 V)
Example: 2 × 400 W in series, Voc 37 V each → 74 V × 1.15 = 85 V ✓

Start check: panel Vmp ≥ battery voltage + 5 V
24 V: one 400 W panel (Vmp ~31 V) is borderline, two in series are better

5.7 DC-DC converter (24 V, optional)

I_in = (20 A × 13.2 V) / (24 V × 0.9) ≈ 12 A → 15 A fuse, 4 mm²

5.8 Branch fuses

A fuse protects the cable. Rate it at or below the cable's ampacity and at or above about 1.25 × the device's maximum current. Place it as close to the busbar as possible, within about 18 cm.


6. Bill of materials

6.0 Price summary per configuration

Budget to mid-range parts, German street prices, autumn 2026, excluding tools (about €200–350 once). Calculated exactly like the 3D model, which shows the same breakdown for whatever you select. "All options" includes the MPPT, two 430 W solar panels with cables and mounts, and the 12 V/USB outputs.

24 V with the default 2000 W inverter:

Battery Count Energy All options Without solar and 12 V/USB
50 Ah 1 1.28 kWh €1,250–2,460 (use a 1000 W inverter) €910–1,720
50 Ah 2 2.56 kWh €1,670–3,090 €1,330–2,360
100 Ah 1 2.56 kWh €1,420–2,700 €1,080–1,960
100 Ah 2 5.12 kWh €2,010–3,570 €1,670–2,840
100 Ah 3 7.68 kWh €2,510–4,280 €2,170–3,540
200 Ah 1 5.12 kWh €1,820–3,200 €1,480–2,460
200 Ah 2 10.24 kWh €2,810–4,570 €2,470–3,840
200 Ah 3 15.36 kWh €3,710–5,780 €3,370–5,040
300 Ah 1 7.68 kWh €2,270–3,800 €1,930–3,060
300 Ah 3 23.04 kWh €5,060–7,580 €4,720–6,840

12 V with the default 1500 W inverter:

Battery Count Energy All options Without solar and 12 V/USB
100 Ah 2 2.56 kWh €1,480–2,810 €1,160–2,100
200 Ah 1 2.56 kWh €1,320–2,490 €1,000–1,790
200 Ah 2 5.12 kWh €1,880–3,350 €1,560–2,640
300 Ah 1 3.84 kWh €1,520–2,720 €1,200–2,020
400 Ah 1 5.12 kWh €1,720–2,990 €1,400–2,290
400 Ah 2 10.24 kWh €2,680–4,350 €2,360–3,640

48 V with the default 3000 W inverter:

Battery Count Energy All options Without solar and 12 V/USB
50 Ah 2 5.12 kWh €2,420–4,210 €2,080–3,460
100 Ah 1 5.12 kWh €2,020–3,640 €1,670–2,890
100 Ah 2 10.24 kWh €3,020–5,110 €2,680–4,360
100 Ah 3 15.36 kWh €3,940–6,400 €3,590–5,650
200 Ah 1 10.24 kWh €2,870–4,740 €2,520–3,990
200 Ah 2 20.48 kWh €4,720–7,310 €4,380–6,560

One 48 V 50 Ah battery (50 A BMS) can't supply a 3000 W inverter; use 1500 W or two batteries.

Modular version: add about €60–110 for 1 module, €90–160 for 2 and €120–210 for 3 (module cases, Anderson plugs, link cables, rolling base).

Breakdown for the recommended setup (24 V, one 100 Ah battery, 2000 W, all options):

Part Qty Price
LiFePO4 battery 25.6 V 100 Ah 1 €450–600
Battery fuse on the + terminal 1 €25–70
Pure sine inverter 2000 W 1 €200–350
AC charger 1 €70–220
MPPT solar charge controller 1 €50–120
Solar input (Anderson SB50) 1 €12–20
Solar panels, 2 × 430 W rigid, cables, mounts 1 €160–380
DC-DC converter 24 → 12 V 1 €25–60
12 V blade fuse block 1 €15–35
USB-C PD 100 W module 1 €20–35
12 V socket 1 €8–15
Voltmeter display 1 €8–15
Battery switch, panel-mount 1 €20–60
Battery shunt 1 €30–130
Busbars, + and − 2 €30–60
230 V outlet 1 €8–15
Fused AC inlet 1 €8–15
Ventilation: grille, fan, thermostat 1 €20–50
Inline fuses and holders (charger, MPPT, 12 V feed, fan, shunt sense, spare set) 6 €48–90
Cables, lugs, heat shrink, glands 1 €132–172
Enclosure, wheels, straps, covers 1 €80–190
Total €1,420–2,700

Premium brands (Victron battery, inverter and charger) can roughly double the total.

6.0b Compared with prebuilt power stations

Street prices seen in German and Austrian shops, September–October 2026. Sales often cut them by 20–40%, so check current prices. Solar input is the maximum the unit accepts.

Model Energy AC output Solar input Price seen €/kWh
EcoFlow DELTA 3 Plus 1.02 kWh 1800 W 1000 W €735–840 ~€770
Bluetti AC180 1.15 kWh 1800 W — €545–699 ~€540
EcoFlow DELTA 3 Plus + extra battery 2.05 kWh 1800 W 1000 W €1,285–1,390 ~€650
Bluetti AC200L 2.05 kWh 2400 W 1200 W €1,179–1,399 ~€630
Anker SOLIX C2000 Gen 2 2.05 kWh 2400 W — €1,099–1,499 ~€630
Anker SOLIX F2000 2.05 kWh 2300 W 1000 W €1,260–1,499 ~€670
Anker SOLIX F3800 3.84 kWh 6000 W 2400 W €2,999 ~€780
EcoFlow DELTA Pro 3 4.10 kWh 4000 W 1600 W €2,800–3,598 ~€780
Anker SOLIX F2000 + expansion battery 4.10 kWh 2300 W 1000 W €2,598 ~€630
Bluetti AC200L + B300K 4.81 kWh 2400 W 1200 W €2,271–2,491 ~€500
Bluetti AC200L + 2 × B300K 7.58 kWh 2400 W 1200 W €3,363–3,583 ~€460
Anker SOLIX F3800 + expansion battery 7.68 kWh 6000 W 2400 W ~€5,700 ~€740
EcoFlow DELTA Pro 3 + extra battery 8.19 kWh 4000 W 1600 W €4,950–6,100 ~€670
EcoFlow DELTA Pro 3 + 2 extra batteries 12.29 kWh 4000 W 1600 W €7,100–8,600 ~€640

How DIY compares per kWh with the cheapest similar prebuilt option (mid-range prices; with solar, the same two panels are added to both sides):

DIY setup (24 V) Energy DIY €/kWh Cheapest similar prebuilt Result
1 × 100 Ah, all options 2.56 kWh ~€805 Bluetti AC200L + panels, ~€760 Prebuilt about 6% cheaper
1 × 100 Ah, no solar/12 V 2.56 kWh ~€594 Bluetti AC200L, ~€629 DIY about 6% cheaper
2 × 100 Ah, all options 5.12 kWh ~€545 AC200L + B300K + panels, ~€551 About the same
1 × 200 Ah, all options 5.12 kWh ~€490 AC200L + B300K + panels, ~€551 DIY about 11% cheaper
3 × 100 Ah, all options 7.68 kWh ~€442 AC200L + 2 × B300K + panels, ~€494 DIY about 10% cheaper
1 × 300 Ah, all options 7.68 kWh ~€395 AC200L + 2 × B300K + panels, ~€494 DIY about 20% cheaper
2 × 200 Ah, all options 10.24 kWh ~€360 DELTA Pro 3 + 2 batteries + panels, ~€661 DIY about 45% cheaper
3 × 200 Ah, all options 15.36 kWh ~€309 Largest listed is 12.3 kWh DIY about 35–45% cheaper per kWh

Conclusion: below about 3 kWh, a prebuilt unit on sale costs about the same or less than DIY. From about 5 kWh, DIY gets clearly cheaper per kWh (about 10–20% less), and from 10 kWh about 30–45% less. Prebuilt units add a warranty, an app, built-in UPS switchover on most models and no assembly; DIY adds repairability, standard parts and easy expansion.

6.1 Core system, 24 V, 1 battery (option B: separate inverter + charger)

# Part Budget option Approx. € Premium option Approx. €
1 LiFePO4 battery 25.6 V 100 Ah, BMS ≥100 A, low-temp cut-off, parallel-capable LiTime, Ective, Redodo 450–600 Victron Smart LiFePO4 (needs external BMS) 1,200+
2 Pure sine inverter 1200–2000 W, 24 V, idle under 15 W Ective CSI, Offgridtec 200–350 Victron Phoenix Smart 24/2000 800–900
3 AC charger 29.2 V LiFePO4 LiTime 10 A 70 Victron Blue Smart IP22 24/16 180–220
4 Battery fuse 125 A, mounted on the + terminal MRBF terminal fuse (check 24 V rating) 25 Class T + holder bolted to the terminal 50–70
5 Battery switch, ≥300 A, panel-mount type with a removable knob (mounted through the side wall) Generic 20–30 Blue Sea m-Series / e-Series 40–60
6 Busbars, ≥150 A, M8 studs (2×), with covers Generic 30 Victron Lynx / Blue Sea 60+
7 Battery shunt (optional) Generic 500 A 30 Victron SmartShunt 500 A 120–130
8 Inline fuse holders + fuses (MIDI/ANL) 2–3 × 20–30 Blue Sea 50
9 Schuko panel socket — 8 Weatherproof 15
10 Fused IEC C14 inlet — 8 — 15
11 Enclosure, wheels (see section 11) — 60–150 — 150+
12 Ventilation: 80–120 mm 24 V fan, thermostat switch (~40 °C), intake grille with dust filter, 2 A fuse — 20–30 Quiet fan (Noctua or similar) 40–50
13 Battery tie-down straps or brackets, terminal covers, busbar covers — 15–25 — 30–40
Subtotal core ~€980–1,200 ~€2,650–2,900

6.2 Optional modules

Module Parts Approx. €
Solar input MPPT 100/20 (avoid cheap "MPPT" units that are really PWM), 30 A fuse, Anderson SB50 panel connector, 6 mm² + 4 mm² solar cable 80–160
12 V / USB outputs DC-DC 24/12-20, 15 A fuse, blade fuse block, USB-C PD 100 W module, 12 V socket, voltmeter, cables 70–130
Automatic switchover Victron MultiPlus 24/1600/40 or MultiPlus-II 24/3000/70 instead of items 2 and 3, plus VE.Bus Smart dongle (~€80) +400–700 net
Plug-in ATS Instead of MultiPlus, with a separate inverter (option B3) 30–100
Remote monitoring Victron Cerbo GX or a Bluetooth-only setup 0–250

6.3 Cable and connectors (1 battery, all modules)

Item Quantity Approx. €
35 mm² flexible cable, red + black 2 m each 40–50
6 mm² red + black 2 m each 10
4 mm² red + black 3 m each 10
4 mm² solar cable red + black 2 m each 8
2.5 mm² twin 3 m 6
0.75 mm² twin 1 m 2
3 × 1.5 mm² H05VV-F (AC) 2 m 6
Copper tube lugs M8 for 35 mm², M6/M8 for branches 30–40 pcs 20
Adhesive-lined heat shrink, red + black set 10
Ferrules, cable ties, clips, cable glands, labels set 15

6.4 Each additional battery (inside the same box)

Item Approx. €
Identical 25.6 V 100 Ah battery 450–600
Battery fuse 125 A (Class T or rated MRBF) 25–70
2 × 35 mm² cables, same length as the other batteries' cables, with lugs 20–30
Per battery ~€500–700
Once, for 2 or more batteries: + and − collector busbars, ≥250 A 40–80
Once, if you have 2–3 batteries: 25–30 A charger upgrade (or MultiPlus) 150–300

6.5 12 V version: what changes

Item 12 V part Approx. €
Battery 12.8 V 200 Ah, BMS 200 A 400–550
Inverter 1000–1500 W, 12 V 150–300
Charger 14.6 V 20 A 70–100
MPPT 100/30 60–150
DC-DC Not needed. Fuse block fed from busbars via 30 A fuse −25 to −60
Main cable 70 mm² 90–110
Battery fuse 200 A Class T or MRBF 25–70

Search terms are in German because they find more results in German shops. The links open a search on idealo (price comparison across many shops) and Amazon.de; specialist shops often have better advice and genuine parts. The 3D model shows the same links next to every part in its cost breakdown and in each component card, with the search terms adjusted to your voltage, battery and inverter.

Part Search terms Search links Also sold by
LiFePO4 battery (24 V 100 Ah) LiFePO4 24V 100Ah Bluetooth idealo · Amazon.de Battery brands' EU shops, solar and camper shops
Battery fuse Class T Sicherung 125A / MRBF Polsicherung 125A idealo · Amazon.de Marine and solar shops
Pure sine inverter Wechselrichter reiner Sinus 24V 2000W idealo · Amazon.de Solar shops, Victron dealers
AC charger LiFePO4 Ladegerät 24V idealo · Amazon.de Solar and camper shops
MPPT Victron SmartSolar MPPT 100/20 idealo · Amazon.de Victron dealers, solar shops
Solar panels Solarmodul 430W idealo · Amazon.de Local solar wholesalers, DIY stores
DC-DC converter DC DC Wandler 24V 12V 20A idealo · Amazon.de Victron dealers, camper shops
12 V fuse block Sicherungsblock 6-fach Flachsicherung Minusschiene idealo · Amazon.de Marine and camper shops
USB-C PD module USB-C PD 100W Einbausteckdose 12V idealo · Amazon.de Camper shops
12 V socket 12V Einbausteckdose Marine idealo · Amazon.de Camper and marine shops
Battery switch Batterietrennschalter 300A idealo · Amazon.de Marine shops
Shunt Victron SmartShunt 500A idealo · Amazon.de Victron dealers
Busbars Sammelschiene 250A M8 Abdeckung idealo · Amazon.de Marine and solar shops
230 V outlet Schuko Einbausteckdose Klappdeckel idealo · Amazon.de Electrical wholesalers
AC inlet (internal charger) Kaltgeräte Einbaustecker mit Sicherung idealo · Amazon.de Electronics shops
Charge, solar and link connectors Anderson SB50 Einbaugehäuse / Anderson SB175 Einbaugehäuse idealo · Amazon.de Electronics and forklift-battery suppliers
Fan and thermostat 24V Lüfter 120mm / Thermostat KSD9700 idealo · Amazon.de Electronics shops
Inline fuses MIDI Sicherungshalter idealo · Amazon.de Marine and camper shops
Cables and lugs Batteriekabel 35mm² / Kabelschuhe M8 35mm² idealo · Amazon.de Electrical wholesalers, welding suppliers
Stackable boxes stapelbare Werkzeugkoffer Set idealo · Amazon.de DIY stores, tool shops (a box set can cost about €50)
Mounting plates, lining Aluminiumblech 2mm Zuschnitt / Kalziumsilikatplatte idealo · Amazon.de Metal suppliers, stove/fireplace shops

Tips:

7. Tools and consumables

Tool Why Approx. €
Hydraulic crimper (10–120 mm²) Reliable lugs on 35/70 mm² cable. Hammer crimpers are not good enough 35–60
Cable cutter for large cables Clean cuts without crushing 20–30
Ratchet crimper (ferrules, small lugs) Branch cables 20–30
Wire stripper — 10–20
Multimeter, ideally with DC clamp Polarity, voltages, current 30–70
Torque wrench (2–25 Nm) Terminal torque per manufacturer 40–60
Heat gun Heat shrink 20–30
Insulated tools (VDE 1000 V) Prevents shorts on battery terminals 30–50
Paint pen Torque marks on nuts, so loosening is visible 3
Pre-charge resistor (25–50 Ω, 10 W) with leads Prevents arcing when connecting the inverter 5
Safety glasses, gloves — 10
Plug-in energy meter Measure your loads 15
Thermometer or cheap thermal camera (optional) Find hot connections 20–200

8. Battery bank: one battery or several

8.1 One battery

flowchart LR
  BP[Battery +] --> F[125 A fuse on the terminal] --> SW[Battery switch, side wall] --> PB[+ busbar]
  BN[Battery −] --> SH[Shunt, battery side to load side] --> NB[− busbar]
  F -. sense wire with 1 A fuse .-> SH

The fuse sits directly on the battery terminal, so not a single centimetre of cable is unprotected. The switch is mounted through the side wall, so you can turn everything off from outside.

8.3 The shunt's voltage-sense wire

Monitors like the Victron SmartShunt have a thin red lead (often labelled Vbatt+ or B+). It measures battery voltage and powers the shunt electronics.

8.2 Two or three batteries in parallel (same box)

flowchart LR
  B1P[Battery 1 +] --> F1[Fuse] --> PC[+ collector]
  B2P[Battery 2 +] --> F2[Fuse] --> PC
  B3P[Battery 3 +] --> F3[Fuse] --> PC
  PC --> SW[Battery switch, side wall] --> PB[+ busbar]
  B1N[Battery 1 −] --> NC[− collector]
  B2N[Battery 2 −] --> NC
  B3N[Battery 3 −] --> NC
  NC --> SH[Shunt] --> NB[− busbar]

Rules:

  1. Identical batteries: same model and capacity, ideally the same batch. The manufacturer must allow parallel use (check the maximum number, often 4).
  2. One fuse per battery, mounted directly on its + terminal.
  3. Equal cable length and size from every battery to the collector busbars. In a compact box the batteries sit at different distances from the collectors, so cut every battery cable to the length of the longest run and loop the extra neatly on the shorter ones.
  4. The − collector goes to the battery side of the shunt, so the shunt measures the whole bank. Nothing else lands on the battery side.
  5. Equalize before the first connection: charge every battery to 100% on its own and let them rest a few hours. Voltages should match within 0.05 V.
  6. Collector rating: at least the total possible current (24 V: ≥250 A).
  7. Adding a battery later: fully charge the new battery and the existing bank separately, then connect. An older bank and a new battery work together, but the bank behaves like its weakest battery.
  8. Weight: about 22 kg per battery. A box with 3 batteries weighs about 85–90 kg (see section 11).
Batteries 24 V bank Energy Runtime at 100 W
1 25.6 V 100 Ah 2.56 kWh ~18 h
2 25.6 V 200 Ah 5.12 kWh ~37 h
3 25.6 V 300 Ah 7.68 kWh ~55 h

Series (2 × 12 V → 24 V): only if the manufacturer explicitly allows it. It needs balancing between batteries. Prefer a single 24 V battery.


9. Wiring diagram

Shown for option B with all optional modules and 2 batteries. With one battery, the collectors disappear: the battery's terminal fuse connects straight to the switch, and battery − straight to the shunt.

flowchart LR
  B1[Battery 1] -- "+ via 125 A fuse" --> PC[+ Collector]
  B2[Battery 2] -- "+ via 125 A fuse" --> PC
  B1 -- "−" --> NC[− Collector]
  B2 -- "−" --> NC
  PC -- "35 mm²" --> SW[Battery switch<br>side wall]
  SW -- "35 mm²" --> PB[+ Busbar]
  NC -- "35 mm²" --> SH[Shunt]
  SH -- "35 mm²" --> NB[− Busbar]
  PC -. "sense wire 0.75 mm², 1 A fuse" .-> SH

  PB -- "35 mm²" --> INV[Inverter]
  NB -- "35 mm²" --> INV
  INV -- "3×1.5 mm²" --> AC[230 V outlet]

  ACIN[Fused IEC inlet] --> CHG[AC charger]
  CHG -- "4 mm², 20 A fuse" --> PB
  CHG --> NB

  PV[Solar input, optional] -- "4 mm² solar" --> MPPT[MPPT 100/20]
  MPPT -- "6 mm², 30 A fuse" --> PB
  MPPT --> NB

  PB -- "4 mm², 15 A fuse" --> DCDC[DC-DC 24→12 V, optional]
  NB --> DCDC
  DCDC --> FB[12 V fuse block]
  FB -- "10 A" --> USB[USB-C 100 W]
  FB -- "15 A" --> S12[12 V socket]
  FB -- "1 A" --> VM[Voltmeter]

With a MultiPlus (option A), the inverter and charger become one device: one pair of DC cables to the busbars, wall plug to its AC input, your outlet strip on its AC output.

Key rules


10. Cable and fuse table

24 V

Connection Cable Fuse Notes
Battery + (terminal fuse) → switch, or → + collector 35 mm² red 125 A per battery, on the terminal Equal lengths with several batteries
+ collector → switch 35 mm² red Covered by battery fuses Short, switch is on the side wall next to it
Battery − → shunt (or → − collector) 35 mm² black — Equal lengths with several batteries
Collectors → switch / shunt 35 mm² Covered by battery fuses —
Switch → + busbar, shunt → − busbar 35 mm² — —
Busbars → inverter 35 mm² Covered by battery fuses Under 1.5 m, equal lengths
Busbars → MultiPlus 24/1600 (option A) 16–25 mm² (per manual) Per manual, often 100–125 A —
Busbars → AC charger 15 A 4 mm² 20 A —
Busbars → external charge input (SB50, blue) 4 mm² 20 A Instead of the internal charger
Busbars → MPPT 6 mm² 30 A —
Solar input → MPPT 4 mm² solar Only with 3+ strings in parallel —
Busbars → DC-DC input 4 mm² 15 A —
DC-DC → 12 V fuse block 4 mm² — Short run
Fuse block → USB-C / 12 V socket / voltmeter 2.5 / 2.5 / 0.75 mm² twin 10 / 15 / 1 A —
Inverter → Schuko outlet 3 × 1.5 mm² Inverter internal PE to inverter earth stud
+ busbar → exhaust fan (via thermostat) 0.75–1 mm² 2 A 24 V fan
Battery side of switch → shunt sense terminal 0.75 mm² red 1 A at the battery + end Keeps the shunt powered with the switch off
IEC inlet → charger 3 × 1.5 mm² In the inlet —

The 24 V main-cable rows above assume a 2000 W inverter. For other sizes use the table in section 5.3.

12 V differences

Connection Cable Fuse
Battery, collector, inverter cables 50 mm² at 1500 W, 95 mm² at 2000 W (section 5.3) 175 A / 250 A per battery
Charger 20 A 6 mm² 25 A
MPPT 30 A 10 mm² 40 A
12 V fuse block feed (no DC-DC) 6 mm² 30 A

Every cable for the recommended setup: 24 V, one 100 Ah battery, 1500 W inverter, internal charger, solar and 12 V/USB, all in one box. Main cables are 25 mm² because the inverter is 1500 W; with a 2000 W inverter use 35 mm² as in the table above. Cables are numbered in build order (section 12). Cut lengths come from the 3D model layout plus about 10% slack, so lay each cable in your box before cutting it.

For any other setup, open the 3D model and expand Cable list in the overview card. It lists every cable, length and termination for what you select, and each part's card shows the cables connected to it.

# From → to Cable Cut length Ends Fuse
1 Battery − → shunt (battery side) 25 mm² black 55 cm M8 lug → M10 lug —
2 Shunt (load side) → − busbar 25 mm² black 20 cm M10 lug → M8 lug —
3 Battery + (terminal fuse) → battery switch 25 mm² red 95 cm M8 lug → M10 lug 100 A on the battery terminal
4 Battery switch (battery side) → shunt sense terminal 0.75 mm² red 30 cm M10 lug → ferrule 1 A inline, at the switch end
5 Battery switch → + busbar 25 mm² red 35 cm M10 lug → M8 lug —
6 Busbars → inverter 25 mm² red + black 35 cm each M8 lug → M8 lug Covered by the battery fuse
7 Busbars → AC charger 4 mm² red + black 60 cm each M6 lug → ferrule 20 A inline on +
8 IEC inlet → charger AC input 3 × 1.5 mm² H05VV-F 50 cm Ferrules In the inlet
9 Busbars → MPPT battery terminals 6 mm² red + black 75 cm each M6 lug → ferrule 30 A inline on +
10 Solar input (Anderson SB50) → MPPT PV terminals 4 mm² solar red + black 30 cm each Anderson contact → ferrule —
11 Busbars → DC-DC input 4 mm² red + black 50 cm each M6 lug → ferrule 15 A inline on +
12 DC-DC output → 12 V fuse block 4 mm² red + black 10 cm each Ferrules —
13 Fuse block → USB-C PD module 2.5 mm² twin 55 cm Ferrules 10 A in the fuse block
14 Fuse block → 12 V socket 2.5 mm² twin 45 cm Ferrules 15 A in the fuse block
15 Fuse block → voltmeter 0.75 mm² twin 45 cm Ferrules 1 A in the fuse block
16 Busbars → exhaust fan (through the thermostat) 0.75 mm² twin 80 cm M6 lug → ferrule 2 A inline on +
17 Inverter AC output → Schuko outlet 3 × 1.5 mm² H05VV-F 55 cm Ferrules Inverter internal; PE to the inverter earth stud

Cable to buy

Totals of the cut lengths above. Add about 0.5 m per size for mistakes and re-crimps.

Cable Total
25 mm² red 1.6 m
25 mm² black 1.1 m
6 mm² red + black 0.8 m each
4 mm² red + black 1.2 m each
4 mm² solar cable red + black (inside the box) 0.3 m each
2.5 mm² twin 1.0 m
0.75 mm² twin 1.3 m
0.75 mm² red 0.3 m
3 × 1.5 mm² H05VV-F 1.1 m

The cable from the solar panels to the SB50 input is extra and depends on where the panels are.

Lugs and ferrules to buy

Termination Count
Copper tube lugs 25 mm², M8 8
Copper tube lugs 25 mm², M10 4
Ring lug 0.75 mm², M10 (shunt sense wire at the switch) 1
Ring lugs 4–6 mm², M6 (charger, DC-DC, MPPT at the busbars) 6
Ring lugs 0.75 mm², M6 (fan at the busbars) 2
Ferrules 0.75 / 1.5 / 2.5 / 4 / 6 mm² 1 assorted box

Stud sizes are typical: M8 on battery terminals, busbars and inverter, M10 on the battery switch and SmartShunt. Check them on your own parts before buying lugs. Stack at most 2 to 3 lugs per stud, biggest lug at the bottom.


11. Housing: enclosure, layout and mounting

11.1 Choose the enclosure type

Type Best for Pros Cons
Aluminium transport box (Zarges, Alutec, 80–120 L) 1 battery, portable Robust, non-combustible, lockable Cut vents and panel openings yourself
Rolling flight case / tool trolley 1–2 batteries Wheels and handles built in Usually wood or plastic: line with metal
Plywood box Budget Cheap, easy to modify Combustible: line inside with steel sheet or fire board
Stackable modules (battery box + electronics box) 2–3 batteries, still movable Each part under 25–35 kg More connectors (Anderson SB175 / SB350)
Stationary: wall board + steel battery cabinet or shelf 2–3 batteries at home Cool, tidy, easy to service, ideal with a MultiPlus Not portable

Rule of thumb: 1 battery → portable box. 2–3 batteries → stationary, or modules.

Inside dimensions chosen by the 3D model (24 V, 2000 W inverter, internal charger, with clearances; check against your actual parts). "Wall" means the inverter is wall-mounted.

Battery Count All options (solar + 12 V/USB) No solar, no 12 V/USB Approx. total weight
50 Ah 1 53 × 56 × 31 cm 38 × 60 × 32 cm (wall) 22 kg
50 Ah 3 67 × 72 × 31 cm 61 × 71 × 31 cm 46 kg
100 Ah 1 57 × 64 × 32 cm (wall) 57 × 59 × 31 cm 31 kg
100 Ah 2 63 × 92 × 31 cm 53 × 91 × 31 cm 52 kg
100 Ah 3 73 × 92 × 31 cm 73 × 91 × 31 cm 73 kg
200 Ah 1 56 × 70 × 32 cm (wall) 56 × 65 × 31 cm 48 kg
200 Ah 2 67 × 91 × 31 cm 61 × 90 × 31 cm 86 kg
200 Ah 3 91 × 91 × 31 cm 91 × 90 × 31 cm 124 kg
300 Ah 1 56 × 70 × 41 cm (wall) 38 × 95 × 41 cm (wall) 67 kg
300 Ah 3 91 × 91 × 41 cm 91 × 90 × 41 cm 181 kg

An external charger saves a few more centimetres in most setups (for one 100 Ah battery with solar and 12 V/USB: 63 × 59 × 31 cm with the inverter on the floor). 12 V sizes are within a few centimetres of these. Choose an enclosure about 5 cm larger in each direction for cable glands, handles and mounting. Above about 50 kg, plan for a stationary setup or split the batteries into separate modules.

11.2 Compact layout

The layout uses two rows with a wiring strip between them, so every main cable is short:

flowchart TB
  BW[Back wall: AC inlet and solar input, low] --> R1
  subgraph R1[Back row]
    BAT[Batteries] --- C12[DC-DC and fuse block, if they fit here]
  end
  R1 --> ST
  subgraph ST[Wiring strip]
    COL[+ and − collectors] --- SH[Shunt] --- BUS[+ and − busbars]
  end
  ST --> R2
  subgraph R2[Front row]
    CHG[Charger and MPPT] --- INV[Inverter, or wall-mounted on the right side wall]
  end
  R2 --> FP[Front panel: outputs high, inputs low]
  SWL[Battery switch, left side wall] -.- ST
  FAN[Exhaust fan, high, left side wall] -.- R2
  VENT[Air intake, low, next to the inverter] -.- R2

How the parts are arranged:

Clearances

Where Minimum
Between any two parts 3 cm
Around the inverter and charger 5 cm
Between parts and the case walls 4 cm (room for cables to the panel and for airflow)
Above the battery terminals 8–10 cm (for cable bends and fuse access)

11.3 Making it safe

11.4 Making it practical


11.5 Building the boxes

Choose the material

Material Weight (box for 1 battery) Pros Cons Use when
Aluminium transport box (Zarges, Alutec), 1–1.5 mm 5–8 kg Non-combustible, robust, lockable, ready-made handles Openings must be cut, sizes fixed Single portable box
Birch multiplex plywood 12–15 mm, aluminium corner profiles 8–12 kg Any size, easy to cut and mount parts on Combustible: line it (see below) Custom sizes, modular stacks
Steel cabinet or sheet-metal box 10–20 kg Best fire protection Heavy, harder to work Stationary installations

Fire lining for wooden boxes: 0.5–1 mm galvanised steel sheet or 6–10 mm calcium silicate board under and around the batteries, and behind the inverter. Fix it with screws, not glue alone.

Size the box

  1. Take the inside dimensions from the 3D model (intro card, or section 11.1).
  2. Add 5 cm in width and depth for cable glands, latches and tolerance.
  3. Height: tallest part plus 8–10 cm for cables and fuse access above the battery terminals. The lid must never touch a terminal.
  4. For a modular stack, every module gets the same footprint so they stack flush.

Example cut list, single box for 24 V 1 × 100 Ah with all options and the inverter wall-mounted (inside 57 × 64 × 32 cm → box 62 × 69 × 37 cm inside), 15 mm plywood:

Part Qty Size (cm)
Base 1 65.0 × 72.0
Front and back panels 2 65.0 × 37.0
Side panels (fit between front and back) 2 69.0 × 37.0
Lid 1 65.0 × 72.0
Removable mounting board, 15–18 mm 1 60.0 × 67.0
Inverter mounting plate, 2–3 mm aluminium 1 about 34 × 20 (inverter length + 4 cm × its depth + 4 cm)

Openings and cut-outs

Always use the cut-out sizes from each part's datasheet. Typical values:

Part Typical cut-out Position
Schuko panel socket about 50 × 50 mm or Ø 56 mm (depends on frame) Front, high
12 V panel socket Ø 28–30 mm Front, high
USB-C PD module Ø 24–30 mm round or per datasheet Front, high
Voltmeter per datasheet (often 45 × 26 mm) Front, high
Fused IEC C14 inlet about 27 × 48 mm Next to the charger, low
Anderson SB50 charge input (blue, external charger) per panel housing datasheet Low, next to the solar input
Anderson SB50 solar input (panel housing) per housing datasheet Next to the MPPT, low
Battery switch (panel-mount) Ø 22–25 mm shaft hole plus 2 screw holes Left side wall at the strip
Anderson SB175/SB350 module ports (modular) per panel housing datasheet Left side, stacked
Air intake grille 80 × 40 mm or larger, with filter mat Low, next to the inverter
Exhaust fan Ø fan size (80–120 mm) + 4 screw holes High, opposite side

Ventilation rule of thumb: about 50 cm² free intake area and one 80–120 mm fan per 2000 W of inverter, intake and exhaust on opposite sides, mesh against insects.

Mounting inside

Handles, wheels and labels

Box build steps

  1. Plan with the 3D model; write down the inside dimensions and wall openings.
  2. Cut the panels; drill and cut every opening before assembly.
  3. Glue and screw the box together; add aluminium corner profiles.
  4. Fit the fire lining.
  5. Seal or paint the wood.
  6. Fit handles, castors (or rolling base), lid hardware and latches.
  7. Mount the panel parts (sockets, inlets, switch, grille, fan) with their gaskets.
  8. Build the electronics on the mounting board, test it on the bench, then bolt it in.
  9. Strap in the batteries last, with the switch off and the battery fuses out.
  10. Label everything, then follow section 14 to commission.

11.6 Modular design

For systems over about 35 kg, split the system into parts that one person can lift. In the 3D model, press Modular.

flowchart TB
  subgraph STACK[Modular stack]
    direction TB
    E[Electronics module, about 15 kg, one port per battery]
    M2[Battery module 2, about 26 kg]
    M1[Battery module 1, about 26 kg]
    RB[Rolling base, 4 castors]
    E ~~~ M2 ~~~ M1 ~~~ RB
  end
  M1 -->|own link cable, same length| E
  M2 -->|own link cable, same length| E

Electronics module: inverter, charger, MPPT, DC-DC converter, fuse block, battery switch (side wall), shunt and main busbars, collector busbars only with 2 or more battery modules, all outlets and inlets, ventilation, and one battery port per module (plus a spare if you plan to expand). About 25 cm high.

Each battery module: one battery strapped down, its fuse on the + terminal inside the module, and one Anderson socket on the same side as the electronics ports. Use SB175 when the battery fuse is up to 175 A, SB350 above that.

Wiring:

Rules:

Sizes from the 3D model (internal charger; heights include a 5 cm base). The model keeps the smallest stack volume:

Setup All options Without solar and 12 V/USB Heaviest part
1 × 24 V 100 Ah 67 × 37 × 63 cm 59 × 36 × 63 cm ~26 kg
2 × 24 V 100 Ah 67 × 37 × 96 cm 59 × 36 × 96 cm ~26 kg
3 × 24 V 100 Ah 67 × 37 × 129 cm 59 × 36 × 129 cm ~26 kg
2 × 24 V 200 Ah 58 × 40 × 103 cm (inverter on wall) 58 × 38 × 96 cm ~43 kg
2 × 48 V 100 Ah (rack) 53 × 57 × 80 cm 50 × 55 × 80 cm ~50 kg

With all options the electronics now sit in one row (inverter, charger with MPPT, 12 V parts side by side), which makes every module 8 cm wider but 18 cm shallower than the two-row layout of version 7: about 23% less stack volume (for 2 × 100 Ah: 67 × 37 × 96 cm instead of 59 × 55 × 96 cm). For 24 V 200 Ah batteries, a wall-mounted inverter gives the smallest stack.

Modular build steps: build the electronics module first (section 12, steps 1–8 without batteries), then each battery module (battery, terminal fuse still out, short cables to its socket), make the link cables, charge every module to 100%, stack, plug in with the switch off, insert the fuses and commission (section 14).

11.7 Toolbox stack (stackable tool-brand boxes)

The modular design also works with stackable toolbox systems: one toolbox per battery plus one for the electronics. In the 3D model, choose Housing: Toolbox stack; the intro card then checks whether your setup fits the two toolboxes below.

How the boxes connect:

flowchart LR
  subgraph BB[Battery toolbox]
    B[Battery] -->|+| F[Fuse on the + terminal]
    F --> S1[SB175 socket, left side]
    B -->|−| S1
  end
  subgraph EB[Electronics toolbox]
    S2[SB175 port, left side] -->|+| SW[Battery switch] --> PB[+ busbar]
    S2 -->|−| SH[Shunt, battery side] --> NB[− busbar]
  end
  S1 ==>|external link cable, main cable size, plugs both ends| S2

Connect and disconnect:

flowchart LR
  C1[Battery switch off] --> C2[Latch the boxes together] --> C3[Plug in the link cable] --> C4[Battery switch on]
  D1[Loads off, battery switch off] --> D2[Unplug the link cable] --> D3[Unlatch the boxes]

What goes where:

Electronics toolbox (top) Battery toolbox (bottom)
Inverter (1000–1500 W recommended), busbars, shunt with sense wire (collectors only with 2+ battery boxes) Battery strapped to a base plate
Battery switch through the side wall, SB175 port Fuse on the + terminal, SB175 socket
Optional MPPT and solar input (SB50 grey), DC-DC, fuse block, USB/12 V Optional SB50 charge socket (blue)
230 V outlet, charge input (SB50 blue), intake grille, exhaust fan Fire lining (steel sheet or calcium silicate)

Mount everything on an internal aluminium or plywood plate bolted through the walls with backing plates; plastic walls must never carry the parts.

Toolboxes checked (inside dimensions and ratings from manufacturer and retailer data, autumn 2026):

Toolbox Inside (L × W × H) Load rating Seal
Milwaukee Packout XL (48-22-8429) 48.5 × 37.1 × 35.3 cm 45 kg IP65
DeWalt ToughSystem 2.0 DS400 (DWST08400) about 49.5 × 31.9 × 34.6 cm 110 lb (about 50 kg) IP65
Milwaukee Packout rolling box (48-22-8427), as a bottom box outside 56 × 46 × 50 cm (inside not published) 250 lb IP65

What fits (3D model, 24 V, external charger, 1500 W):

Setup Each box needs (inside) Packout XL ToughSystem DS400
1 × 24 V 50 Ah, no solar, no 12 V/USB 39 × 35 cm; battery box 33 cm, electronics box 25 cm high ✓ ✗ (too shallow)
2 × 24 V 50 Ah (two battery boxes) 47 × 35 cm ✓ ✗ (too shallow)
1 × 24 V 50 Ah with solar and 12 V/USB 40 × 53 cm ✗ ✗
24 V 100 Ah (standard batteries are about 52–53 cm long) about 59 × 35 cm ✗ ✗

So a toolbox stack works best for 24 V 50 Ah modules (1.28 kWh each) with an external charger and no extras; add more 50 Ah battery boxes for more energy. For a 100 Ah battery, use a larger box, the modular stack with custom boxes, or a two-tier box.

Two-tier single box (alternative): one tall box with the battery on the floor and an aluminium deck above it on four corner posts carrying the electronics. The battery cables pass through a grommeted gap in the deck. With an external charger it needs about 44 × 34 × 56 cm (24 V 50 Ah) or 63 × 36 × 56 cm (24 V 100 Ah) inside, which is taller than most toolboxes.

Toolbox price: a stackable storage box set can cost about €50 (the 3D model uses €50 for the set plus €15–30 per box for base plates, mounting plates and fire lining). Tool-brand XL boxes cost about €110–170 each if you need larger inside dimensions.

Toolbox-specific rules:


12. Build steps

Before you start: battery switch off, every battery fuse removed. Remove watches and rings. Use insulated tools. Cover terminals you aren't working on.

Making a good lug (every main cable)

  1. Cut cleanly with a cable cutter.
  2. Strip exactly the depth of the lug barrel.
  3. Twist strands lightly; don't trim any.
  4. Insert fully and crimp with the matching die.
  5. Pull test: it must not move.
  6. Adhesive-lined heat shrink over the barrel.
  7. Torque to spec (M8 battery terminals often 8–12 Nm), then add a paint-pen mark across nut and stud. No washers between lug and terminal.

Steps

flowchart TD
  S1[1. Mount the parts, switch off, fuses out] --> S2[2. Negative main]
  S2 --> S3[3. Positive main and shunt sense wire]
  S3 --> S4[4. Inverter]
  S4 --> S5[5. Charger or charge input]
  S5 --> S6[6. MPPT: battery side first, then solar]
  S6 --> S7[7. 12 V side and exhaust fan]
  S7 --> S8[8. 230 V output]
  S8 --> S9[9. DC system ground]
  S9 --> S10[10. Fuses in and power up]
Step What Details
1 Mount the parts Everything screwed down before any cable, with the clearances from section 11. Cut the side-wall hole and mount the battery switch, the intake grille and the exhaust fan. Strap the batteries down. With several batteries: charge each to 100% on its own first
2 Negative main 1 battery: battery − → shunt → − busbar. Several: each battery − → − collector (equal lengths) → shunt → − busbar
3 Positive main Fuse holder bolted onto each battery + terminal (fuse still out). 1 battery: terminal fuse → battery switch (side wall) → + busbar. Several: each terminal fuse → + collector (equal lengths) → battery switch → + busbar. Then the shunt sense wire: 1 A fuse at the switch input stud → 0.75 mm² → shunt sense terminal
4 Inverter (or MultiPlus) Floor: in its column, terminals towards the busbars. Wall: bolt the mounting plate to the right side wall 12–17 cm above the floor, hang the inverter with its terminal end towards the busbars. Then:
4 Inverter DC Busbars → inverter, equal and short. Double-check polarity: reversed polarity destroys most inverters instantly
5 AC charger or charge input External charger: SB50 socket (blue) → 20 A fuse → + busbar, − to − busbar. Internal: + busbar → 20 A fuse → charger. IEC inlet → charger AC input. (Skip with MultiPlus)
6 MPPT (optional) Battery side first (6 mm², 30 A fuse), then solar input. Never connect PV to an MPPT without the battery
7 12 V side (optional) + busbar → 15 A fuse → DC-DC → fuse block → USB-C, 12 V socket, voltmeter
7a 48 V notes Class T battery fuses only, DC parts rated for at least 60 V, and an isolated DC-DC converter unless its manual allows a shared negative
7b Exhaust fan + busbar → 2 A fuse → thermostat → 24 V fan → − busbar (12 V system: from the fuse block)
8 230 V output Inverter → Schuko outlet, 3 × 1.5 mm². Brown L, blue N, green/yellow PE. PE to the inverter earth stud and to a metal enclosure. See section 16
9 DC system ground Per inverter manual, usually one connection from the − busbar to the earth stud
10 Fuses in, power up See below

Powering up the first time

flowchart TD
  P1[Check polarity with a multimeter] --> P2[Check torque marks and lug covers]
  P2 --> P3[Pre-charge the inverter through the resistor]
  P3 --> P4[Insert the first fuse, remove the resistor]
  P4 --> P5[Insert the remaining battery fuses]
  P5 --> P6[Battery switch on]
  P6 --> P7{BMS app: voltage correct, no alarms?}
  P7 -->|Yes| P8[Commissioning tests, section 14]
  P7 -->|No| P9[Switch off, find the fault]
  1. Check polarity of every connection with a multimeter.
  2. Check every nut has a torque mark and every lug is covered.
  3. Pre-charge the inverter: its input capacitors draw a huge spike and cause a loud spark. Bridge one empty battery fuse holder (or the open switch) with the 25–50 Ω resistor for 5–10 seconds, until the voltage across the resistor is near 0 V. Then insert the fuse or close the switch, and remove the resistor.
  4. Insert the remaining battery fuses.
  5. Switch on, check the BMS app: voltage correct, no alarms, all batteries visible.
  6. Continue with section 14.

13. Settings for every device

LiFePO4 values (per cell × 8 for 24 V, × 4 for 12 V, × 16 for 48 V). Your battery datasheet overrides these.

Setting Per cell 24 V 12 V 48 V
Absorption / bulk 3.55 V 28.4 V 14.2 V 56.8 V
Absolute maximum 3.65 V 29.2 V 14.6 V 58.4 V
Absorption time — 30–60 min, or tail current 2–5% of Ah same same
Float 3.375 V or off 27.0 V 13.5 V 54.0 V
Equalization — Off Off Off
Temperature compensation — Off Off Off
Inverter low-voltage cut-off 3.0 V 24.0 V 12.0 V 48.0 V
Inverter restart 3.2 V 25.6 V 12.8 V 51.2 V
Low-temperature charging — Blocked below 0 °C same same

14. Commissioning and testing

Tick each item and note values in the test log (section 23).

  1. [ ] Voltages correct at battery, busbars and inverter input.
  2. [ ] Battery switch works from outside: off means 0 V on the + busbar.
  3. [ ] BMS: no alarms, cell voltages within 0.05 V. With several batteries: voltages within 0.05 V of each other.
  4. [ ] Charger: AC plugged in, charging current visible.
  5. [ ] MPPT (if fitted): charging in daylight.
  6. [ ] DC-DC (if fitted): 13.0–13.5 V at the 12 V socket. USB-C charges a phone and a laptop.
  7. [ ] Inverter at no load: about 230 V AC, note the idle draw.
  8. [ ] Small load: 60 W lamp for 10 minutes.
  9. [ ] Fridge: starts reliably several times.
  10. [ ] Full load: heater or kettle at the inverter's rating for 10 minutes. Then feel every lug, cable and fuse. Anything clearly warmer than the rest is a bad connection: switch off and redo it.
  11. [ ] With several batteries: under load, the current per battery should be within about 10–15% of each other.
  12. [ ] Fan: warm the thermostat (hair dryer) and check the fan starts; check air comes out at the top.
  13. [ ] Switchover test (MultiPlus or ATS): with the fridge and router running, unplug the wall input. They must keep running. Plug it back in: no interruption.
  14. [ ] RCD test if fitted (see section 16).
  15. [ ] Drain test: run your real blackout loads until cut-off. Compare runtime with your calculation.
  16. [ ] Recharge fully, note the charge time.
  17. [ ] Re-torque main terminals after 1–2 weeks and check torque marks.

15. Using it in a blackout

Preparation

During an outage

flowchart TD
  O1{Switchover option?} -->|A, B2 or B3| O3[Nothing to do, devices keep running]
  O1 -->|B1 manual| O2[Plug fridge, router and lamp into the box]
  O2 --> O4[Start large loads one after another]
  O3 --> O4
  O4 --> O5[Check state of charge every few hours]
  O5 --> O6{Below 30 percent?}
  O6 -->|Yes| O7[Cut non-essential loads, run the freezer in blocks]
  O6 -->|No| O5
  O7 --> O8[Sunny? Put the solar panels out]
  1. With option B1, plug the essential devices into the box. With A, B2 and B3, nothing to do.
  2. Start large loads one after another (fridge, wait a minute, freezer).
  3. Open fridge and freezer as little as possible. Run the freezer in blocks if the outage lasts.
  4. Check state of charge every few hours. At 30%, cut non-essentials.
  5. If sunny and you have solar: panels out.

What it can and can't run

Can run Can't run (or only briefly)
Fridge, freezer, router, lights, phones, laptops, TV, gas boiler controls and pump, CPAP Electric heating, heat pumps, electric water heaters, ovens, induction hobs, washing machines (heating phase)

16. Earthing, RCDs and gas boilers


17. Fire safety



19. Maintenance and storage

Interval Task
Monthly Check state of charge and BMS alarms
Every 3 months Run real loads for 1–2 hours. With a MultiPlus or ATS, repeat the switchover test
Every 6 months Visual check of lugs, cables, fuses, torque marks; clean fans, vents and filters
Every 12 months Re-torque main terminals; full discharge/charge cycle to recalibrate the shunt; firmware updates; test the RCD
After heavy use Feel lugs and cables for heat

Storage:


20. Common mistakes

Mistake Why it's a problem Do this instead
Hammer-crimped or soldered main lugs High resistance, heat, loosening Hydraulic crimper, pull test
Washer between lug and terminal Reduced contact area, heat Lug directly on the terminal, washer on top
ANL or MIDI fuse as battery fuse Can't break a LiFePO4 short circuit Class T (or MRBF where rated)
Fuse far from the battery The cable before the fuse is unprotected Within 15 cm or on the terminal
Loads connected to the battery side of the shunt Wrong state of charge Only battery negatives on the battery side
Batteries paralleled at different charge levels Large equalizing currents Charge each to 100% first
Unequal battery cables One battery does most of the work Equal lengths and sizes
Charger left on lead-acid profile Overcharge, equalization damages LiFePO4 LiFePO4 profile, equalization off
PV connected to MPPT before the battery Can damage the MPPT Battery first
Solar and charge inputs with the same plug colour Panels plugged into the charge input bypass the MPPT Grey for solar, blue for charging, red for battery links
Wall-mounted inverter on thin plywood with wood screws Tears out when the box is carried Mounting plate bolted through with a backing plate
Inverter oversized "just in case" High idle draw shortens blackout runtime Size to real loads plus margin
Inverter output plugged into a house socket Backfeed, deadly for line workers Extension leads or an electrician-installed changeover
No pre-charge Arcing, pitted contacts Pre-charge resistor
Battery switch buried inside the box You can't switch off quickly in an emergency Mount it through the side wall
Parts packed edge to edge Heat builds up, fuses can't be reached 3 cm between parts, 5 cm around inverter and charger
Cables routed over other batteries' terminals Short circuit risk when servicing Each battery's cables leave over its own top only
No airflow path Inverter derates or shuts down in summer Intake low, exhaust fan high on the opposite side

21. Troubleshooting

Symptom Likely cause Fix
Inverter shuts off when the fridge starts Surge too high, or voltage dip Check BMS current limit and lugs; bigger inverter or second battery
Low-voltage alarm although the battery shows 40% Voltage drop in cables or a bad lug Compare voltage at battery vs. inverter under load; over 0.3 V means a bad connection
One lug gets hot Poor crimp or loose nut Switch off, recrimp, retorque
BMS cuts off while charging Charge voltage too high or one cell high Absorption 28.2–28.4 V, check cell balance
BMS off and won't restart Over-discharge protection Apply the charger to wake it
No charging in winter Low-temperature protection Warm the battery above 5 °C
Shunt state of charge drifts Not synchronized, or something bypasses the shunt Full charge; check the battery side of the shunt
MPPT doesn't charge PV voltage too low, or battery not detected Check Vmp vs. battery voltage; battery before PV
Parallel batteries share current unevenly Unequal cables, bad lug, or one battery older Equal cables, check lugs, compare BMS data
Fridge restarts at every grid failure ATS too slow, or no UPS mode MultiPlus with UPS function on, or always-on inverter
RCD on output never trips in a test Floating output Section 16
Gas boiler won't ignite No N-PE reference or polarity Section 16, call an electrician

22. Alternatives and upgrade paths

Option When it makes sense Approx. cost
This build, 24 V, 1–3 batteries 2.5–7.5 kWh, up to 2 kW, best DIY price per kWh €1,150 + €500–700 per extra battery
MultiPlus instead of inverter + charger Fridge and router keep running with no action +€400–700
48 V server-rack batteries (5 kWh, stackable; now in the 3D model) More than 5 kWh or 3 kW €900–1,200 per 5 kWh + 48 V inverter/charger
Prebuilt power station (EcoFlow, Anker, Bluetti) on sale Warranty, UPS function, compact, no wiring €450–700 per kWh
Balcony solar with battery Mainly lowering your bill; many don't power your home in an outage Check the backup function before buying
Electrician-installed home battery with backup Whole-house or circuit-level backup €6,000+

23. Checklists and quick reference card

23.1 Decisions to make before buying

23.2 Shopping checklist

23.3 Test log

Date Test Expected Measured OK
Battery voltage(s) 26.4–27.2 V when full
Inverter idle draw under 15 W
Full-load test, hottest lug hand-warm at most
Current split between batteries within 10–15%
Switchover test no interruption
Drain test runtime calculated: ___ h
Recharge time calculated: ___ h

23.4 Quick reference card

Print this and keep it with the box.

SYSTEM: 24 V LiFePO4, ___ batteries, ___ kWh, inverter ___ W
SWITCHOVER: MultiPlus / ATS / always-on / manual

BATTERY SWITCH: red knob on the LEFT SIDE of the box = emergency off

TURN ON:   Battery switch ON → BMS app check → inverter ON → devices
TURN OFF:  Devices off → inverter OFF → battery switch OFF

BLACKOUT ORDER: fridge → (1 min) → freezer → router → lights
DON'T RUN: heaters, kettles, ovens, washing machines

STATE OF CHARGE: 100% full | 30% cut non-essentials | inverter stops at 24.0 V

CHARGING: wall ~7 h per battery (15 A charger) | solar: battery first, then PV

FUSES: Battery 125 A each | Charger 20 A | MPPT 30 A | DC-DC 15 A
       USB-C 10 A | 12 V socket 15 A | Display 1 A | Fan 2 A

NEVER: plug into a house socket | charge below 0 °C | work on it switched on

SMOKE OR HOT SMELL: side-wall switch OFF only if safe → leave, close door → call 112

24. Revision notes

Version 13

Area Version 12 Version 13
Safety Spread across sections 16–20 Separate safety guide: electricity basics, step-by-step sizing of inverter, fuses and cables, all values for 24 V 100 Ah, battery/AC/fire/charging safety, inspections, emergencies, checklists
Recommended inverter 2000 W 1500 W for one 24 V 100 Ah battery (headroom to the 100 A BMS)
3D model — Safety checklist in the intro card (live checks for BMS, fuses, voltage drop, weight) and a safety note on every component and cable card; 1500 W default

Version 12

Area Version 11 Version 12
Buying Prices only New 6.6: German search terms, idealo and Amazon.de search links, shop types and buying tips; the 3D model shows the same links per part
Toolbox stack price €130–200 per tool-brand box €50 box set plus €15–30 per box for plates and lining
3D model Settings reset on reload Choices are saved in the browser, with a reset button; final review: all cards, steps, prices and cables scanned in 792 configurations without broken values

Version 11

Area Version 10 Version 11
Single-battery modular and toolbox stacks Collector busbars always present Removed with one battery module: port straight to the switch and shunt; explanation why the main busbars can't replace collectors with 2+ modules
Toolbox sizes 44 × 35 cm for 1 × 50 Ah 39 × 35 cm (shorter wiring strip), 2 × 50 Ah added
Wall-mounted inverter Sockets could be pushed beside it Box keeps enough front-panel width next to the inverter

Version 10

Area Version 9 Version 10
Diagrams Several drawn as text Every diagram and flow is a Mermaid diagram: switchover options, external charger, battery bank, layout, modular stack, toolbox connection, plus new decision, build-order, power-up and blackout flows
Toolbox stack — New 11.7: external link cable between toolboxes, what goes in each box, toolboxes checked, fit table, two-tier alternative, toolbox rules
3D model Two-tier box with internal cables Toolbox stack with an external SB175 link cable and a built-in fit check; every component card lists its connections, example parts and corrected details

Version 9

Area Version 8 Version 9
Layout optimiser Floor vs one wall position, chosen by footprint Floor, wall beside and wall above the floor parts, lengthwise/sideways batteries, columns front/back/split; chosen by smallest inside volume
Wall-mounted inverter Terminals down, 16 cm high, needed extra depth Terminals facing into the box near the busbars, 12–17 cm high; sockets moved left; battery cables in their own lane
Single box, 1 × 24 V 100 Ah, all options 67 × 60 × 31 cm 57 × 64 × 32 cm (−6% volume)
Modular stack, 2 × 24 V 100 Ah, all options 59 × 55 × 96 cm 67 × 37 × 96 cm (−23% volume)
Battery switch Terminal studs about 9 cm above the floor About 7 cm, so cables pass under a wall-mounted inverter
Review 628 configurations 1,256 configuration runs (auto, wall and floor mounting) without overlaps or cables through parts

Version 8

Area Version 7 Version 8
Charger Internal only New 3.1: external charger through a fused SB50 charge input, colour coding, wiring, rules; cut-outs, cable table, build step, prices
Inverter mounting Floor only Floor or wall-mounted on the side wall; the 3D model builds both and keeps the smaller box
Box sizes Floor layout Wall-mount sizes for modular stacks (7–18% less volume), external-charger single box
Box building — Mounting plate and through-bolting for a wall-mounted inverter
Review 246 configurations 628 configurations checked automatically (all voltages, both mounts, internal and external charger, single and modular): no overlaps, no cables through parts

Version 7

Area Version 6 Version 7
System voltage 12 V and 24 V 48 V added everywhere: comparison, batteries, inverter/fuse table, prices, settings, notes
Housing Enclosure types and layout only New 11.5: materials, sizing, cut list, cut-outs, ventilation sizing, mounting, lid, handles, labels, box build steps
Modular design Only in the 3D model New 11.6: layout, module contents, star wiring, connector choice, rules, sizes and weights, build steps
Prices 12 V and 24 V 48 V table and modular surcharge added
Review v4 report New full review (separate report): 246 configurations checked automatically

Version 6

Area Version 5 Version 6
Battery sizes 100 Ah only, drawn about 40% too small in the model (32 × 18 cm) 50–300 Ah (24 V) and 100–400 Ah (12 V) with real dimensions and weights, section 5.0
Inverter Fixed 2000 W (24 V) / 1500 W (12 V) 1000–3000 W selectable; fuse, cable and price per size, section 5.3; BMS limit check
12 V main fuse/cable at 1500 W 200 A, 70 mm² 175 A, 50 mm² (same sizing rule as 24 V); 250 A, 95 mm² at 2000 W
Box sizes 41–71 cm per side Recalculated with real battery sizes: 53–91 cm per side, 42 cm high with 300 Ah
Prices Totals without panels Totals for many battery/count combinations; solar module now includes two 430 W panels
Prebuilt — Section 6.0b: 14 prebuilt setups from 1 to 12 kWh with solar input, and a per-kWh comparison

Version 5

Area Version 4 Version 5
Shunt Main connections only New section 8.3: voltage-sense wire to the battery side of the switch with a 1 A fuse; added to diagrams, cable table, build step 3, prices and the 3D model

Version 4 (prices and final review)

Area Version 3 Version 4
Prices Per-part tables only, subtotal didn't include ventilation and straps Section 6.0: totals for every configuration plus a full breakdown, identical to the 3D model
Budget in section 1 €1,150–1,350 Updated to match the full parts list
Fan Wiring step only Fan fuse added to the quick reference card; fan wiring shown in the 3D model
Review — Separate review report with findings and fixes

Version 3 (layout review)

Area Version 2 Version 3
Battery switch Inside the box, in the middle of the wiring Panel-mount switch through the left side wall, operable from outside
Battery fuse (1 battery) Separate fuse holder near the battery Fuse mounted directly on the + terminal, same as with several batteries
Layout Long single board, 100–170 cm Compact two-row layout with a wiring strip; parts rearranged per configuration; 41–71 cm per side
Clearances Not specified 3 cm between parts, 5 cm around heat sources, 4 cm to walls
Ventilation "Vents low and high" Intake grille next to the inverter, thermostat exhaust fan high on the opposite wall, wiring step 7b
Batteries "Secure with straps" Straps shown and listed in the BOM
Wall connections Everything on one panel Outputs high, inputs low, inputs next to the charger column
Equal battery cables Assumed by layout Cut to the longest run, loop the extra
Checks — Switch-off test from outside, fan test, new common mistakes

Version 2

Changes from version 1, based on a review of the first guide:

Area Version 1 Version 2
Multiple batteries External packs plugged into the main unit Batteries inside the same box with + and − collector busbars, one fuse per battery and equal cable lengths (matches the 3D model)
Battery fuse "Class T or MRBF" without limits Breaking-capacity table: MRBF only where rated at your voltage, never ANL/MIDI
Switchover One sentence New section 3 comparing manual, always-on, ATS and MultiPlus, with costs and a test
Inverter size 2000 W recommended 1200–2000 W, since smaller units have lower idle draw for typical blackout loads
Solar and 12 V outputs Part of the core build Optional modules with separate costs
Housing Layout only New section 11: enclosure types, sizes, weights, safety and convenience
Cable sizing Free-air ampacity Added 20% derating inside a closed box and MultiPlus cable sizes
Runtime Formulas only Real-life corrections (cold, ageing, low-load efficiency, DC loads), freezer block tip, slider in the 3D model
DC ground Missing Single-point DC system ground per inverter manual
Earthing Short note Section 16: floating vs. bonded output, RCD, boiler polarity
Fire safety Card said "no water on electrical equipment" Corrected: CO2 for small electrical fires, leave battery fires to the fire brigade, AVD option
Commissioning — Added current-split check for parallel batteries, switchover test, RCD test, torque marks
New sections — Common mistakes, decision and shopping checklists, test log